Module containing the HeatExchangerController class.
"""
import logging
import numpy as np
from pandapipes import call_lib
from pandaprosumer.controller.base import BasicProsumerController
from pandaprosumer.constants import CELSIUS_TO_K, TEMPERATURE_CONVERGENCE_THRESHOLD_C
from pandaprosumer.mapping import FluidMixMapping
from pandaprosumer.library.heat_exchanger_utils import compute_temp
logger = logging.getLogger()
[docs]
class HeatExchangerController(BasicProsumerController):
"""
Controller for Heat Exchanger systems.
The heat exchanger is implemented from KS conservation and logarithmic mean temperature difference (LMTD)
In the heat exchanger element some nominal temperatures and mass flows are specified.
The resulting return temperature on the primary side is calculated from this state,
then the primary mass flow is deducted.
The temperature on the primary side must be higher than on the secondary (t_in_1 > t_out_2 and t_out_1 > t_in_2).
Primary:
t_in_1 = t_hot_1 = t_feed_1
t_out_1 = t_cold_1 = t_return_1 (result of _compute_temp)
Secondary:
t_in_2 = t_cold_2 = t_return_2
t_out_2 = t_hot_2 = t_feed_2
:param prosumer: The prosumer object
:param heat_exchanger_object: The heat exchanger object
:param order: The order of the controller
:param level: The level of the controller
:param in_service: The in-service status of the controller
:param index: The index of the controller
:param kwargs: Additional keyword arguments
"""
def name_class(self):
return "heat_exchanger_controller"
def __init__(self, prosumer, stratified_heat_storage_object, order, level,
in_service=True, index=None, name=None, **kwargs):
"""
Constructor method
"""
super().__init__(prosumer, stratified_heat_storage_object, order=order, level=level, in_service=in_service,
index=index, name=name, **kwargs)
primary_fluid = self._get_element_param(prosumer, 'primary_fluid')
secondary_fluid = self._get_element_param(prosumer, 'secondary_fluid')
if primary_fluid and primary_fluid != prosumer.fluid.name:
self.primary_fluid = call_lib(primary_fluid)
else:
self.primary_fluid = prosumer.fluid
if secondary_fluid and secondary_fluid != prosumer.fluid.name:
self.secondary_fluid = call_lib(secondary_fluid)
else:
self.secondary_fluid = prosumer.fluid
self.t_previous_1_out_c = np.nan
self.t_previous_1_in_c = np.nan
self.mdot_previous_1_kg_per_s = np.nan
# FixMe: Fix the mapping (generic or fluid mix) and how to handle _mdot_feedin_kg_per_s
@property
def _t_feed_in_c(self):
if not np.isnan(self.input_mass_flow_with_temp[FluidMixMapping.TEMPERATURE_KEY]):
return self.input_mass_flow_with_temp[FluidMixMapping.TEMPERATURE_KEY]
else:
return self.inputs[:, self.input_columns.index("t_feed_in_c")][0]
@property
def _mdot_1_provided_kg_per_s(self):
if not np.isnan(self.input_mass_flow_with_temp[FluidMixMapping.MASS_FLOW_KEY]):
return self.input_mass_flow_with_temp[FluidMixMapping.MASS_FLOW_KEY]
else:
return np.nan
def _t_m_to_receive_init(self, prosumer):
"""
Return the expected received Feed temperature, return temperature and mass flow in °C and kg/s
:param prosumer: The prosumer object
:return: A Tuple (Feed temperature, return temperature and mass flow)
"""
t_feed_demand_c, t_return_demand_c, mdot_demand_kg_per_s = self.t_m_to_deliver(prosumer)
if not np.isnan(self.t_previous_1_out_c):
return self.t_previous_1_in_c, self.t_previous_1_out_c, self.mdot_previous_1_kg_per_s
else:
delta_t_hot_default_c = self._get_element_param(prosumer, 'delta_t_hot_default_c')
return self.t_m_to_receive_for_t(prosumer, t_feed_demand_c + delta_t_hot_default_c)
[docs]
def t_m_to_receive_for_t(self, prosumer, t_feed_c):
"""
For a given feed temperature in °C, calculate the required feed mass flow and the expected return temperature
if this feed temperature is provided.
:param prosumer: The prosumer object
:param t_feed_c: The feed temperature
:return: A Tuple (Feed temperature, return temperature and mass flow)
"""
t_out_2_required_c, t_in_2_required_c, mdot_tab_required_kg_per_s = self.t_m_to_deliver(prosumer)
mdot_2_required_kg_per_s = sum(mdot_tab_required_kg_per_s)
t_1_in_c = t_feed_c
if mdot_2_required_kg_per_s < 1e-6 or abs(t_out_2_required_c - t_in_2_required_c) < 1e-3:
# If the secondary mass flow is too low, no heat is exchanged
t_1_out_c = t_1_in_c
mdot_1_kg_per_s = 0
else:
(mdot_1_kg_per_s, t_1_in_c, t_1_out_c,
mdot_2_kg_per_s, t_2_in_c, t_2_out_c) = self.calculate_heat_exchanger(prosumer,
t_out_2_required_c,
t_in_2_required_c,
mdot_2_required_kg_per_s,
t_1_in_c)
if not np.isnan(self.t_previous_1_out_c):
# FixMe: This doesn't make sense
mdot_previous_1_in_kg_per_s = self.mdot_previous_1_kg_per_s
assert mdot_previous_1_in_kg_per_s >= 0
assert self.t_previous_1_in_c >= self.t_previous_1_out_c
return self.t_previous_1_in_c, self.t_previous_1_out_c, mdot_previous_1_in_kg_per_s
assert not np.isnan(t_1_in_c)
assert not np.isnan(t_1_out_c)
assert not np.isnan(mdot_1_kg_per_s)
assert mdot_1_kg_per_s >= 0, f"Heat Exchanger {self.name}: Negative mass flow {mdot_1_kg_per_s} kg/s at timestep {self.time} in prosumer {prosumer.name}"
assert t_1_in_c >= t_1_out_c
return t_1_in_c, t_1_out_c, mdot_1_kg_per_s
[docs]
def calculate_heat_exchanger(self, prosumer, t_2_out_c, t_2_in_c, mdot_2_kg_per_s, t_1_in_c):
"""
Main Heat Exchanger calculation method
:param prosumer: The prosumer object
:param t_2_out_c: The secondary output (hot feed pipe) temperature
:param t_2_in_c: The secondary input (cold return pipe) temperature
:param mdot_2_kg_per_s: The secondary mass flow
:param t_1_in_c: The primary input (hot feed pipe) temperature
"""
t_1_hot_nom_c = self._get_element_param(prosumer, 't_1_in_nom_c')
t_1_cold_nom_c = self._get_element_param(prosumer, 't_1_out_nom_c')
t_2_cold_nom_c = self._get_element_param(prosumer, 't_2_in_nom_c')
t_2_hot_nom_c = self._get_element_param(prosumer, 't_2_out_nom_c')
mdot_2_nom_kg_per_s = self._get_element_param(prosumer, 'mdot_2_nom_kg_per_s')
delta_t_2_c = t_2_out_c - t_2_in_c
cp_2_j_per_kgk = self.secondary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_2_out_c + t_2_in_c) / 2)
cp_1_j_per_kgk = self.primary_fluid.get_heat_capacity(CELSIUS_TO_K + t_1_in_c)
q_exchanged_w = cp_2_j_per_kgk * mdot_2_kg_per_s * delta_t_2_c
max_q_kw = self._get_element_param(prosumer, 'max_q_kw')
if q_exchanged_w > max_q_kw * 1000:
q_exchanged_w = max_q_kw * 1000
mdot_2_kg_per_s = max_q_kw * 1000 / (cp_2_j_per_kgk * delta_t_2_c)
delta_t_2_nom_c = t_2_hot_nom_c - t_2_cold_nom_c
cp_2_nom_j_per_kg_k = self.secondary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_2_hot_nom_c + t_2_cold_nom_c) / 2)
q_exchanged_nom_w = cp_2_nom_j_per_kg_k * mdot_2_nom_kg_per_s * delta_t_2_nom_c
q_ratio = q_exchanged_w / q_exchanged_nom_w
delta_t_hot_nom_c = t_1_hot_nom_c - t_2_hot_nom_c
delta_t_cold_nom_c = t_1_cold_nom_c - t_2_cold_nom_c
delta_t_hot_c = t_1_in_c - t_2_out_c
# Logarithmic mean temperature difference (LMTD) at nominal conditions
if delta_t_hot_nom_c == delta_t_cold_nom_c:
lmtd_nom = delta_t_hot_nom_c
else:
lmtd_nom = (delta_t_hot_nom_c - delta_t_cold_nom_c) / np.log(delta_t_hot_nom_c / delta_t_cold_nom_c)
a = delta_t_hot_c / (q_ratio * lmtd_nom)
min_delta_t_1_c = self._get_element_param(prosumer, 'min_delta_t_1_c')
max_t_1_out_c = t_1_in_c - min_delta_t_1_c
min_x = 1 - (max_t_1_out_c - t_2_in_c) / delta_t_hot_c
min_a = -np.log(1 - min_x) / min_x if min_x != 0 else 1 # FixMe: case where min_x == 1 or >= 1 ?
if a < min_a:
# If 'a' is too low, q_exchanged_w is too big so reduce mdot_2_kg_per_s
# else t_1_out_c would be hotter than t_1_in_c
a = min_a
q_ratio = delta_t_hot_c / (min_a * lmtd_nom)
q_exchanged_w = q_ratio * q_exchanged_nom_w
mdot_2_kg_per_s = q_exchanged_w / (cp_2_j_per_kgk * delta_t_2_c)
# delta_t_cold = _calculate_cold_temperature_difference(a, delta_t_hot_c)
t_1_out_c = max_t_1_out_c
t_mean_1_c = CELSIUS_TO_K + (t_1_in_c + t_1_out_c) / 2
mdot_1_kg_per_s = q_exchanged_w / (self.primary_fluid.get_heat_capacity(t_mean_1_c) * (t_1_in_c - t_1_out_c))
else:
t_1_out_c, mdot_1_kg_per_s = compute_temp(q_ratio, q_exchanged_w, t_1_in_c, t_2_in_c, t_2_out_c,
delta_t_hot_nom_c, delta_t_cold_nom_c, cp_1_j_per_kgk,
heat_consumer=False)
# If the primary mass flow is too low, no heat is exchanged to the secondary side
# if mdot_1_kg_per_s < 1e-6:
# mdot_2_kg_per_s = 0
# t_2_out_c = t_2_in_c
return mdot_1_kg_per_s, t_1_in_c, t_1_out_c, mdot_2_kg_per_s, t_2_in_c, t_2_out_c
[docs]
def calculate_heat_exchanger_reverse(self, prosumer, t_1_in_c, t_1_out_c, mdot_1_kg_per_s, t_2_in_c):
"""
Heat Exchanger calculation method based on LMTD method from nominal conditions.
Reverse calculation that limit the primary side mass flow.
:param prosumer: The prosumer object
:param t_1_in_c: The input temperature of the fluid in °C
:param t_1_out_c: The output temperature of the fluid in °C
:param mdot_1_kg_per_s: Mass flow rate of the fluid in kg/s
:param t_2_in_c: The input temperature of the secondary side in °C
:return: The output mass flow rate of the secondary side in kg/s,
the input and output temperature of the secondary side in °C,
the output mass flow rate of the primary side in kg/s,
the input and output temperature of the primary side in °C
"""
t_1_hot_nom_c = self._get_element_param(prosumer, 't_1_in_nom_c')
t_1_cold_nom_c = self._get_element_param(prosumer, 't_1_out_nom_c')
t_2_cold_nom_c = self._get_element_param(prosumer, 't_2_in_nom_c')
t_2_hot_nom_c = self._get_element_param(prosumer, 't_2_out_nom_c')
mdot_2_nom_kg_per_s = self._get_element_param(prosumer, 'mdot_2_nom_kg_per_s')
delta_t_fluid_c = t_1_in_c - t_1_out_c
cp_fluid_j_per_kgk = self.primary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_1_in_c + t_1_out_c) / 2)
cp_2_j_per_kgk = self.secondary_fluid.get_heat_capacity(CELSIUS_TO_K + t_2_in_c)
q_exchanged_w = cp_fluid_j_per_kgk * mdot_1_kg_per_s * delta_t_fluid_c
delta_t_2_n = t_2_hot_nom_c - t_2_cold_nom_c
cp_2_nom_j_per_kg_k = self.secondary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_2_hot_nom_c + t_2_cold_nom_c) / 2)
q_exchanged_nom_w = cp_2_nom_j_per_kg_k * mdot_2_nom_kg_per_s * delta_t_2_n
q_ratio = q_exchanged_w / q_exchanged_nom_w
delta_t_hot_nom_c = t_1_hot_nom_c - t_2_hot_nom_c
delta_t_cold_nom_c = t_1_cold_nom_c - t_2_cold_nom_c
t_2_out_c, mdot_2_kg_per_s = compute_temp(q_ratio, q_exchanged_w, t_2_in_c, t_1_in_c, t_1_out_c,
delta_t_hot_nom_c, delta_t_cold_nom_c, cp_2_j_per_kgk,
heat_consumer=True)
# If the primary mass flow is too low, no heat is exchanged to the secondary side
if mdot_2_kg_per_s < 1e-6:
mdot_1_kg_per_s = 0
t_1_out_c = t_1_in_c
t_2_out_c = t_2_in_c
return mdot_1_kg_per_s, t_1_in_c, t_1_out_c, mdot_2_kg_per_s, t_2_in_c, t_2_out_c
def _save_state(self):
"""Backup states before Run"""
self._backup_state = {
"t_previous_1_out_c": self.t_previous_1_out_c,
"t_previous_1_in_c": self.t_previous_1_in_c,
"mdot_previous_1_kg_per_s": self.mdot_previous_1_kg_per_s,
}
def _restore_state(self):
"""Restore states before Rerun"""
if hasattr(self, "_backup_state"):
self.t_previous_1_out_c = self._backup_state["t_previous_1_out_c"]
self.t_previous_1_in_c = self._backup_state["t_previous_1_in_c"]
self.mdot_previous_1_kg_per_s = self._backup_state["mdot_previous_1_kg_per_s"]
[docs]
def control_step(self, prosumer):
"""
Executes the control step for the controller.
:param prosumer: The prosumer object
"""
if not prosumer.rerun:
self._save_state()
else:
self._restore_state()
if not (self.in_service and getattr(prosumer, self.obj.element_name).iloc[
self.obj.element_index[0]].in_service): # FixMe: use gettattr element
self.applied = True
return
super().control_step(prosumer)
if not self._are_initiators_converged(prosumer):
# If some of the initiators are not converged, do not run the control step
self._unapply_initiators(prosumer)
self.input_mass_flow_with_temp = {FluidMixMapping.TEMPERATURE_KEY: np.nan,
FluidMixMapping.MASS_FLOW_KEY: np.nan}
return
t_out_2_required_c, t_in_2_required_c, mdot_tab_required_kg_per_s = self.t_m_to_deliver(prosumer)
mdot_2_required_kg_per_s = sum(mdot_tab_required_kg_per_s)
t_1_in_c = self._t_feed_in_c
assert not np.isnan(t_1_in_c), f"Heat Exchanger {self.name} t_1_in_c is NaN for timestep {self.time} in prosumer {prosumer.name}"
assert not np.isnan(t_out_2_required_c), f"Heat Exchanger {self.name} t_out_2_required_c is NaN for timestep {self.time} in prosumer {prosumer.name}"
assert not np.isnan(t_in_2_required_c), f"Heat Exchanger {self.name} t_in_2_required_c is NaN for timestep {self.time} in prosumer {prosumer.name}"
assert not np.isnan(mdot_2_required_kg_per_s), f"Heat Exchanger {self.name} mdot_2_required_kg_per_s is NaN for timestep {self.time} in prosumer {prosumer.name}"
if mdot_2_required_kg_per_s < 1e-6 or abs(t_out_2_required_c - t_in_2_required_c) < 1e-3:
# If the secondary mass flow is too low, no heat is exchanged
t_1_out_c = t_1_in_c
mdot_1_kg_per_s = 0
mdot_2_kg_per_s = mdot_2_required_kg_per_s
t_2_in_c = t_in_2_required_c
t_2_out_c = t_out_2_required_c
result_mdot_tab_kg_per_s = self._merit_order_mass_flow(prosumer, mdot_2_kg_per_s,
mdot_tab_required_kg_per_s)
else:
# FixMe: case where t_out_2_required_c == t_in_2_required_c
t_out_2_required_c_init = t_out_2_required_c
if t_1_in_c < t_out_2_required_c:
t_out_2_required_c = t_1_in_c - min(self._get_element_param(prosumer, 'delta_t_hot_default_c'), 5)
if t_out_2_required_c < t_in_2_required_c:
t_in_2_required_c += t_out_2_required_c - t_out_2_required_c_init
assert t_1_in_c >= t_out_2_required_c, f"Heat Exchanger {self.name} t_1_in_c < t_out_2_required_c ({t_1_in_c} < {t_out_2_required_c}) for timestep {self.time} in prosumer {prosumer.name}"
assert t_out_2_required_c >= t_in_2_required_c, f"Heat Exchanger {self.name} t_out_2_required_c < t_in_2_required_c ({t_out_2_required_c} < {t_in_2_required_c}) for timestep {self.time} in prosumer {prosumer.name}"
rerun = True
nb_runs = 0
while rerun:
nb_runs += 1
if nb_runs > 20:
raise Exception("Heat Exchanger calculation did not converge after 100 iterations", self.name, self.time, prosumer.name)
(mdot_1_kg_per_s, t_1_in_c, t_1_out_c,
mdot_2_kg_per_s, t_2_in_c, t_2_out_c) = self.calculate_heat_exchanger(prosumer,
t_out_2_required_c,
t_in_2_required_c,
mdot_2_required_kg_per_s,
t_1_in_c)
# ToDo: Manage the case where m_1_kg_per_s_in < mdot_1_kg_per_s
# If the input mass flow is smaller than the one required by the Heat Exchanger,
# The primary return temperature is assumed equal to the secondary cold input
# if m_1_kg_per_s_in < mdot_1_kg_per_s:
# t_1_out_c = t_cold_2
# mdot_1_kg_per_s = m_1_kg_per_s_in
if not np.isnan(self._mdot_1_provided_kg_per_s):
assert self._mdot_1_provided_kg_per_s >= 0, f"Heat Exchanger {self.name} received mass flow is negative for for timestep {self.time} in prosumer {prosumer.name}"
# If the primary is fed with a fixed mass flow (not free air)
if mdot_1_kg_per_s > self._mdot_1_provided_kg_per_s:
# If the primary mass flow is higher than the one required by the Heat Exchanger,
# recalculate the secondary mass flow to reduce the heat demand to reduce the primary mass flow
# delta_t_2_c = t_2_out_c - t_2_in_c
# delta_t_1_c = t_1_in_c - t_1_out_c
# cp_1_j_per_kg_k = self.primary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_1_in_c + t_1_out_c) / 2)
# cp_2_j_per_kg_k = self.secondary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_2_out_c + t_2_in_c) / 2)
# q_exchanged_w = self._mdot_feed_in_kg_per_s * cp_1_j_per_kg_k * delta_t_1_c
# mdot_2_kg_per_s = q_exchanged_w / (cp_2_j_per_kg_k * delta_t_2_c)
# FixMe: The recalculation of the secondary mass flow lead to a higher mass flow, is it ok ?
(mdot_1_kg_per_s, t_1_in_c, t_1_out_c,
mdot_2_kg_per_s, t_2_in_c, t_2_out_c) = self.calculate_heat_exchanger_reverse(prosumer,
t_1_in_c,
t_1_out_c,
self._mdot_1_provided_kg_per_s,
t_2_in_c)
assert abs(mdot_1_kg_per_s - self._mdot_1_provided_kg_per_s) < .01,\
(f"Heat Exchanger {self.name} mdot_1_kg_per_s != self._mdot_1_provided_kg_per_s"
f" ({mdot_1_kg_per_s} != {self._mdot_1_provided_kg_per_s}) for for timestep"
f" {self.time} in prosumer {prosumer.name}")
elif mdot_1_kg_per_s < self._mdot_1_provided_kg_per_s:
# If the primary mass flow is lower than the one required by the Heat Exchanger,
# model a bypass on the primary side where the extra mass flow doesn't exchange heat.
# Recalculate the primary output temperature
mdot_bypass_kg_per_s = self._mdot_1_provided_kg_per_s - mdot_1_kg_per_s
t_bypass_c = t_1_in_c
t_1_out_c = (t_bypass_c * mdot_bypass_kg_per_s + t_1_out_c * mdot_1_kg_per_s) / self._mdot_1_provided_kg_per_s
mdot_1_kg_per_s = self._mdot_1_provided_kg_per_s
result_mdot_tab_kg_per_s = self._merit_order_mass_flow(prosumer,
mdot_2_kg_per_s,
mdot_tab_required_kg_per_s)
rerun = False
if len(self._get_mapped_responders(prosumer)) > 1 and mdot_2_kg_per_s < mdot_2_required_kg_per_s:
# If the heat Pump is not able to deliver the required mass flow,
# recalculate the condenser input temperature, considering that all the downstream elements will be
# still return the same temperature, even if the mass flow delivered to them by the Heat Pump is lower
t_return_tab_c = self.get_treturn_tab_c(prosumer)
if abs(mdot_2_kg_per_s) > 1e-8:
t_2_in_new_c = np.sum(result_mdot_tab_kg_per_s * t_return_tab_c) / mdot_2_kg_per_s
else:
t_2_in_new_c = t_in_2_required_c
if abs(t_2_in_new_c - t_in_2_required_c) > 1:
# If this recalculation changes the condenser input temperature, rerun the calculation
# with the new temperature
t_in_2_required_c = t_2_in_new_c
rerun = True
if mdot_2_kg_per_s > mdot_2_required_kg_per_s:
# If the actual output mass flow is higher than the one required, redistribute the extra mass flow
# to the other downstream elements,
# so the through the secondary side mass flow is the same as the total distributed mass flow
for i in range(len(result_mdot_tab_kg_per_s)):
result_mdot_tab_kg_per_s[i] = result_mdot_tab_kg_per_s[i] + (mdot_2_kg_per_s - mdot_2_required_kg_per_s) / len(result_mdot_tab_kg_per_s)
assert abs(mdot_2_kg_per_s - np.sum(result_mdot_tab_kg_per_s)) < 1e-3, \
(f"Heat Exchanger {self.name} mdot_2_kg_per_s != sum(result_mdot_tab_kg_per_s) "
f"({mdot_2_kg_per_s} != {np.sum(result_mdot_tab_kg_per_s)}) for"
f" timestep {self.time} in prosumer {prosumer.name}")
cp_1_kj_per_kg_k = self.primary_fluid.get_heat_capacity(CELSIUS_TO_K + (t_1_in_c + t_1_out_c) / 2) / 1000
q_exchanged_kw = mdot_1_kg_per_s * cp_1_kj_per_kg_k * (t_1_in_c - t_1_out_c)
result = np.array(
[[q_exchanged_kw, mdot_1_kg_per_s, t_1_in_c, t_1_out_c, mdot_2_kg_per_s, t_2_in_c, t_2_out_c]]
)
self.last_result = {
"q_exchanged_kw": q_exchanged_kw,
"mdot_1_kg_per_s": mdot_1_kg_per_s,
"t_1_in_c": t_1_in_c,
"t_1_out_c": t_1_out_c,
"mdot_2_kg_per_s": mdot_2_kg_per_s,
"t_2_in_c": t_2_in_c,
"t_2_out_c": t_2_out_c,
}
result_fluid_mix = []
for mdot_kg_per_s in result_mdot_tab_kg_per_s:
result_fluid_mix.append({FluidMixMapping.TEMPERATURE_KEY: t_2_out_c,
FluidMixMapping.MASS_FLOW_KEY: mdot_kg_per_s})
assert t_2_out_c >= 0, f"Heat Exchanger {self.name} t_2_out_c is negative ({t_2_out_c}) for timestep {self.time} in prosumer {prosumer.name}"
assert t_2_in_c >= 0, f"Heat Exchanger {self.name} t_2_in_c is negative ({t_2_in_c}) for timestep {self.time} in prosumer {prosumer.name}"
assert t_1_out_c >= 0, f"Heat Exchanger {self.name} t_1_out_c is negative ({t_1_out_c}) for timestep {self.time} in prosumer {prosumer.name}"
assert t_1_in_c >= 0, f"Heat Exchanger {self.name} t_1_in_c is negative ({t_1_in_c}) for timestep {self.time} in prosumer {prosumer.name}"
assert mdot_2_kg_per_s >= 0, f"Heat Exchanger {self.name} mdot_2_kg_per_s is negative ({mdot_2_kg_per_s}) for timestep {self.time} in prosumer {prosumer.name}"
assert mdot_1_kg_per_s >= 0, f"Heat Exchanger {self.name} mdot_1_kg_per_s is negative ({mdot_1_kg_per_s}) for timestep {self.time} in prosumer {prosumer.name}"
assert t_1_out_c <= t_1_in_c, f"Heat Exchanger {self.name} t_1_out_c > t_1_in_c ({t_1_out_c} > {t_1_in_c}) for timestep {self.time} in prosumer {prosumer.name}"
assert t_2_out_c >= t_2_in_c, f"Heat Exchanger {self.name} t_2_out_c < t_2_in_c ({t_2_out_c} < {t_2_in_c}) for timestep {self.time} in prosumer {prosumer.name}"
if np.isnan(self.t_keep_return_c) or mdot_1_kg_per_s == 0 or abs(t_1_out_c - self.t_keep_return_c) < TEMPERATURE_CONVERGENCE_THRESHOLD_C: # or len(self._get_mapped_initiators_on_same_level(prosumer)) == 0:
# If the actual output temperature is the same as the promised one, the storage is correctly applied
self.finalize(prosumer, result, result_fluid_mix)
self.applied = True
self.t_previous_1_out_c = np.nan
self.t_previous_1_in_c = np.nan
self.mdot_previous_1_kg_per_s = np.nan
else:
# Else, reapply the upstream controllers with the new temperature so no energy appears or disappears
# FixMe: Should not do that if the initiators is not on the same level
self._unapply_initiators(prosumer)
self.t_previous_1_out_c = t_1_out_c
self.t_previous_1_in_c = t_1_in_c
self.mdot_previous_1_kg_per_s = mdot_1_kg_per_s
self.input_mass_flow_with_temp = {FluidMixMapping.TEMPERATURE_KEY: np.nan,
FluidMixMapping.MASS_FLOW_KEY: np.nan}